PD602B

Distributed Process Intelligence type, PD 602,  P-NET via Light Link, Ethernet LAN Interface

• Real time clock with battery backup.
• 64 – 1024 Kbytes in circuit programmable FLASH memory for user program.
• 128 – 2048 Kbytes in circuit programmable FLASH memory for user data.
• 64  – 992 Kbytes RAM memory with battery backup for user data. (2 Kbytes of RAM reserved for system variables)
• Built-in replaceable lithium battery.
• LED state indicators.
• Low power consumption.
• Process-Pascal programmable.
• Automatic checksum control of program memory after each Reset.
• EMC approved (89/336/EEC).

Loading…

ORDERING

Picture Part. No. Name Price Quantity


600528 DKK 3,400.00



600529 DKK 5,500.00



600342 DKK 6,000.00



600530 DKK 8,500.00



600399 DKK 250.00



701117 DKK 10.00



701139 DKK 15.00



600217 DKK 100.00



600218 DKK 150.00



Product Description

  • Real time clock with battery backup.
  • 64 – 1024 Kbytes in circuit programmable FLASH memory for user program.
  • 128 – 2048 Kbytes in circuit programmable FLASH memory for user data.
  • 64  – 992 Kbytes RAM memory with battery backup for user data. (2 Kbytes of RAM reserved for system variables)
  • Built-in replaceable lithium battery.
  • LED state indicators.
  • Low power consumption.
  • Process-Pascal programmable.
  • Automatic checksum control of program memory after each Reset.
  • EMC approved (89/336/EEC).

APPLICATION
A PD 602 DPI is used to provide programmable intelligence for the local cluster via Light-Link P-NET, and to provide an interface with local area networks (LAN) using the Ethernet electrical standard (10 Mb/s). The BM 016 Base module is recommended for this device.

The PD 602 DPI is programmed in Process-Pascal, which is an extension of standard Pascal, allowing easy declaration and utilisation of P-NET variables and objects. Programs are developed and compiled on a standard PC, then downloaded directly via a P-NET interface. Program code can be downloaded to FLASH memory.

SPECIFICATIONS
Communication
The PD 602 DPI has 2 standard P-NET Communication Channels.
Channel 1 is a P-NET Ethernet communication channel for connecting the DPI to a LAN.
Channel 2 is a P-NET Light-Link communication channel intended for communicating with other locally mounted P-NET devices using the optical Light-Link interface.

Memory
Program FLASH: 64 – 1024 Kbytes
Data FLASH: 128 – 2048 Kbytes
RAM 64 – 992 Kbytes

Power Specifications
Power Supply DC: nom. 24.0 V
min. 15.0 V
max. 32.0 V
Ripple: max. 5%

Power consumption @ 24Vdc
Operating: max. 50 mA
Current at power up: max. 100 mA

Battery Backup (RAM and RTC)
Replaceable battery (Panasonic) BR1632
Replace battery every 5 years. If the operating ambient temperature is over 50°C, replace battery more frequently.
Backup time @ 25°C typ. 1 year

Environmental Conditions

Ambient Temperature
Operating temperature: -25 °C – 70 °C
Storage temperature: -40 °C – 85 °C

Humidity
Relative humidity: max. 95%

Real Time Clock
Accuracy: Deviation is approx. 3 minutes per month over the full
temperature range.
Deviation is approx. 1 minute per month at 25 °C

Approvals
EMC EN61000-6-2, EN61000-6-3

Vibration IEC 60068-2-6
Frequency range: 2-100 Hz
Frequency / amplitude: 2-10 Hz: +/- 5.0 mm
10-100 Hz: +/- 2g
Sweep rate: max. 1 octave/min
Number of axes: 3 mutually perpendicular

Mounting requirements
The PD 602 DPI must be mounted in a metal enclosure/panel.

 