551 269 01

 

PD 621 6 Channel Digital I/O (Current Sink)

 

New firmware version 1.14

 

CommonIn:

Register 2, Notification in the Service Channel has been extended with a new variable - CommonIn. This variable contains the status of all the Inflags for channels 1 to 6.

 

In many applications, it can be an advantage to read the CommonIn variable instead of reading each Inflag/Outflag within channels 1 – 6, to reduce the number of transmissions made on

P-NET. Setting an output will automatically set the corresponding Inflag within that channel and will therefore have an effect on the variable CommonIn.

 

New functions available in Digital I/O Channel 1- 6:

 

  • Input hold mode
  • Input delay mode
  • Input edge detect mode

 

More details about the new functions can be found by using this link: Functions

 

Output controlled by other channel:

The PD 621 now provides a feature that enables an Output to be controlled by another channel in the module. In applications where very fast reaction times are required, this function becomes very useful. 

 

 

 

The table below shows which output functions that can be controlled by other functions.

 

        Output

Input

Output

mode

Follow

mode

Toggle

output

One shot

output

Duty cycle output

Input mode

 

 

 

X

 

X

 

X

 

 

Input hold mode

 

 

X

 

X

 

X

 

Input delay mode

 

 

X

 

X

 

X

 

Input edge detect mode

 

 

 

X

 

X

 

 

 

 

 

 

 

Output

mode

 

 

X

 

 X

 

X

 

Follow

mode

 

 

X

 

 X

 

X

 

Toggle

output

 

 

X

 

 X

 

X

 

One shot

output

 

 

X

 

X

 

X

 

Duty cycle output

 

 

X

 

X

 

X